- 机房环境(机房专用空调解决方案)建设所面临的问题。
目前,很多广电机房没有使用机房专用空调(常被称为精密空调,恒温恒湿机),而是广泛应用普通舒适性空调。与机房专用空调比较,舒适性空调问题如下:
At present, many broadcasting room does not use the special air conditioning (often called precision air conditioning, constant temperature and humidity air conditioning), but is widely used the ordinary comfort air conditioning. Compared with the room air-conditioning, comfort air conditioning problems is listed as follows:
- 舒适性空调出风温度过低,会导致在出风口附近空气中的水蒸汽饱和凝结出水滴,对附近的用电设备造成很大危险。
- 舒适性空调风量过小,不适合计算机设备的高热密度的发热特点,无法驱除机房的“热岛效应”。
- 舒适性空调温度调节精度过低,温度调节精度为±3~5℃,温度的波动对设备稳定运行极其不利。
- 舒适性空调没有湿度控制功能。舒适性空调无法进行湿度控制。没有加湿功能,只能进行除湿,在冬季甚至过度除湿,湿度过低产生的静电极易产生设备故障。
- 舒适性空调过滤能力无法达到机房标准。舒适性空调只具备简单的过滤功能,其过滤器的过滤效果根本无法达到机房的要求。机房专用空调严格按照0.5 微米/升<18,000(B级)设计,配合以每小时30次的风量循环,保障机房洁净。
- 舒适性空调在北方地区无法实现低温(室外)运行。一般标称-5℃以下即无法制冷和加热,而机房是发热量很大的区域,即使在冬天也需要对设备进行降温。
- 舒适性空调维护量大,舒适性空调长期应用在非设计工况下,故障率高,能效比不断下降,越来越耗能。机房专用空调按照全年长期运行设计,维护量小。
- 舒适性空调在机房内应用,寿命短。在365天/24小时应用的情况下其寿命一般不超过3年(机房专用空调的设计寿命一般为连续运转10年)。
- 舒适性空调耗电量大,机房专用空调选用的工业等级压缩机能效比高达3.3。而舒适性空调目前业界选用的高等级压缩机能效比约2.9,同时考虑到其他设计差异,如显热比指标,舒适性空调比同容量的机房专用空调多耗电20%-30%,不仅增加使用成本,也浪费能源。
以上舒适性空调的问题,将影响机房设备的安全运行,增加机房运行成本,需要应用机房专用空调予以解决。
The problems for comfort air conditioning showing above will affect the safe operation of equipment, and increase the operation cost. Thus, it needs special air conditioner to solve.
- 机房环境系统建设的基本原则及一体化解决方案 (the basic principle of construction and the solution of integration environmental system)
系统设计原则 (the principle of system design)
- 通用性 (general)
- 稳定性 (stable)
- 可维护性(maintenance)
- 智能化设计 (smart design)
- 经济性 (economics)
三、公司的解决方案精髓 (The essence of solutions)
公司作为全球最完整的机房环境整体解决方案供应商。它在整合了网络能源业界最宽、最完整的拥有自主知识产权的产品线的基础上,不但能为客户提供最完整的机房环境产品,从而能为客户提供品质一流的、由全方位的产品组成的综合解决方案。而且,还组建起以“客户为中心”的、完善的客户接待窗口和管理平台,以便为用户提供最优质的售前、售后及长期的維保服务。
As the world's most complete solution provider for computer room is based on the integration of network energy that is most wide, and the most complete products with independent intellectual property rights on the line. It not only can provide the most complete environmental products for customers, but also provide comprehensive solutions to first-class quality and full range of products from the customer. But, also set up a "customer-centric", perfect customer reception window and management platform, in order to provide the best quality pre-sale, customer service and long-term service for users.
四、机房环境(机房专用空调解决方案)建设推荐案例 (Computer room environment (the solution for special air conditioning) recommended case)
某广电IDC中心机房,建筑面积705.6平方米,层高 4.3米,按照功能的要求分为A区、B区、C区及D区,第一消防分区为A区,第二消防分区为B区、C区及D区。如下图:
A radio IDC center, a building area of 705.6 square meters, 4.3 meters tall, according to the functional requirements is divided into A zone, B zone, C zone and D zone. The first fire partition is for A zone. The second fire partition is for B area, C area and D area. The following diagram:
考虑建筑热负荷及设备(计算机等)热负荷, A区所需冷量不小于210KW, B区、C区及D区所需冷量不小于190KW。在这个方案中,如果考虑应用舒适空调,以5P为例,即使不考虑备份,也需要32套,应用中无法达到IDC机房需要的温湿度、洁净度标准。同样中央空调也无法实现这个IDC机房的空气调节要求。合理的机房专用空调应用及设计方案,才能满足机房环境建设的合理性、安全性、可扩容性。此IDC机房空调方案分析如下:
Considering the building heat load and heat load of equipment (computer), A zone required cold quantity that is not less than 210KW, and B, C and D areas required cold quantity that is not less than 190KW. In this scheme, if we consider the application of comfort air conditioning, taking 5HP as an example, even without taking into account the backup, also need 32 sets, the application cannot achieve the requirements of temperature and humidity and IDC room needs of cleanliness standard. The central air-conditioning also cannot achieve the requirements for IDC computer room air conditioning. Reasonable room for air conditioning applications and design will meet the environmental construction which is reasonable, safety, expansibility. Analysis of the IDC computer room air conditioning scheme are as follows:
- A区机房采用4 台机房专用空调产品81UA(其中1台备用),单台机组可制冷量为.77.3KW,可提供总冷量为309.2KW ;B区、C区及D区机房采用4 台65UA机组(其中1台备用),单台机组可制冷量为66.6KW,可提供总冷量为266.4KW,以上推荐配置机组均能完全满足机房冷负荷的要求,并均实现3+1备份,任意机组故障或维护,其它机组正常工作,保障系统安全性。
- 空调机组采用下送风形式,单机送风风量为 15680 立方米/h,主用机组工作实现IDC机房换气次数30.96次,符合IDC机房设备换热特点以及风量设计要求。
- 室外冷凝器按当地照室外环境温度配置;
- 空调机组通过智能通讯接口,直接接入环境监控系统实现远程及本地监控。
- 空调机组自带漏水报警器,对机组附近可能发生的漏水情况进行实时监测及报警。
- 空调机组严格按照标准机房空调环境条件要求进行设计,满足恒温恒湿、噪音、洁净、供电、抗电磁干扰及A级安全等级的要求。
Air conditioning is in strict accordance with the standards of computer room air conditioning environment designed to meet the requirements of constant temperature and humidity, noise, clean, power supply, anti electromagnetic interference and level A of security.
此方案实施后,该机房环境控制良好,设备稳定运行。
After implementing this program, the computer room environment control is good and stable operation of the equipment.
以上推荐方案和实例是Hiross根据目前广电行业发展现状及未来趋势结合我司在网络行业的相关经验提出了的一体化解决方案来应对目前广电行业发展对机房环境系统建设提出的新要求并在部分广电行业客户处得到落实和应用的实例。
The above recommended scheme and example is the integration of Hiross according to the current development status of radio and TV industry related experience and future trends in the internet industry with our proposed solution to the current radio and television industry development put forward new requirements for environment system construction and implementation of room instance and application in electric industry wide customers.